ZW32-12MF Permanent Magnet Vacuum Circuit Breaker
When a fault occurs in the T-connected branch line of a 12kV overhead distribution line or in the end user, the protection action time limit of the incoming switch cannot be reasonably adjusted with the protection time limit of the substation outgoing switch, which will cause the substation outgoing switch to trip. If the fault is permanent and the substation reclosing will fail, a local fault in the medium-voltage user boundary will cause the entire 12kV distribution line to be shut down.
If an outdoor boundary circuit breaker is installed at the T-connection or user end (responsibility boundary point), after confirming that a fault (overcurrent, short circuit, single-phase grounding, etc.) has occurred in the user boundary, the fault is automatically isolated, which can ensure normal power supply to users in non-fault areas.
The application of ZW32-12M outdoor high-voltage permanent magnetic vacuum circuit breaker on 12kV feeder overhead lines can avoid the joint fault power outage of fault-free lines, reduce the scope of fault power outage, shorten the power outage time of users, and protect the safe operation of the main network. It also has fault detection, protection control and communication functions, and can automatically cut off single-phase grounding faults and automatically isolate interphase short-circuit faults. The installation point is used at the responsibility demarcation point of the 12kV distribution line user incoming line, and can also be used at the branch line connection that meets the requirements.
Outline and installation size (mm):
Working Conditions:
Main Technical Parameters of Circuit Breaker:
Project | Parameter | ||
Rated voltage | 12kv | ||
Rated current | 630A, 1250A | ||
Rated frequency | 50Hz | ||
Power frequency withstand voltage (1min) | Dry type (phase to phase, to ground/break) | 42kv / 48kv | |
Wet test (to ground, external insulation) | 34kv | ||
Lightning impulse withstand current (peak value) (phase to phase, to ground/break) | 75kA / 85kA | ||
Rated short-circuit breaking current | 20kA | 25kA | |
Rated short-circuit making current (peak value) | 50kA | 63kA |
Main Mechanical parameters of Circuit Breaker:
Project | Parameter | |
Rated peak withstand current | 50kA | 63kA |
4S short-time withstand current | 20kA | 25kA |
Rated operating cycle | Open -0.3s- Close Open -180s- Close Open | |
Rated short-circuit current breaking times | 30 Times | |
Mechanical life | 30000 Times | |
Secondary circuit 1min power frequency withstand voltage | 2kv | |
Contact opening distance | 9±1 mm | |
Contact overtravel | 2.5 ±1 mm | |
Opening speed | 1.1 ±0.3 m/s | |
Closing speed | 0.6 ±0.2 m/s | |
Contact closing bounce time | ≤ 2 ms | |
Phase center distance | 340 ±2 mm | |
Three-phase opening and closing out of phase | ≤ 2 ms | |
Conductive circuit resistance of each phase | ≤ 80(with isolation ≤ 150) | |
Weight | about 70kg |
If you didn’t know which switchgear system that used to your present project, it’s time to speak to our Industry Experts-Kimball. We’re glad to answer any questions you may have!
”From planning to delivery, it has been a smooth and gratifying transaction. The Dongshenyuan Electric team is quickly responsive, and the quality of DSY Switchgear are top-grade! In the end, they deliver as promised, and more. We look forward to a long-term partnership with them.”
Manufacturer Of Switchgear For Power Distribution and Electricity Generation System In China for 20 years
© 2023 Migor Template Kit – All rights reserved.
Download our catalog to see all products and data sheets, the catalog sheet will be automatically sent to your email address.
Have questions or need a quote? Leave us a message—our experts will get back to you within 24 hours.
Own factory, customized according to demand