Overview:
FZW28F-12 outdoor boundary vacuum load switch (FFK for short) is used in pole-mounted occasions and has manual and electric operation functions. The switch body is maintenance-free and uses vacuum arc extinguishing and SF6 gas as the insulating medium. This product complies with the following standards: GB3804-2004 3.6 ~ 40.5kV high-voltage AC load switch GB/T11022 Common technical requirements for high-voltage switchgear and control equipment standards This manual describes the structure, function and installation and commissioning methods of outdoor boundary vacuum load switches. FZW28F-12 outdoor boundary vacuum load switch has fault detection, protection, control and communication functions. It is installed on a 10kV line and can realize the self-cutting of single-phase grounding faults and automatic isolation of phase-to-phase short-circuit faults. It is suitable for the T-connection or user end of the user incoming line of the 10kV distribution line, and can also be used for other branch line connections that meet the requirements.
Outline and installation size (mm):
Working Conditions:
Rated Parameters of Switchgear:
Project | Parameter | ||
Rated voltage | 12kv | ||
Rated insulation level | 1min power frequency withstand voltage (between poles, to ground/break) | Dry | 42kv |
Wet | 34kv | ||
Lightning impulse voltage (between poles, to ground/break) | 75kv/85kv | ||
Rated current | 630A | ||
Rated short-time withstand current and duration | 16kA/4s | ||
Rated peak withstand current | 40kA | ||
Rated short-circuit making current | 40kA | ||
Mechanical life | 10000 Times | ||
Designed service life | 20 years | ||
Net weight | 210kg | ||
Rated frequency | 50Hz |
Note:
1. When the altitude of the product is higher than 1000m, the insulation withstand voltage should be adjusted accordingly.
2. When the PT is built-in, the inter-electrode withstand voltage is prohibited.
Main Technical Parameters:
Electronic Current Sensor | ||
Rated current ratio | Phase current | 600A/1V |
Zero-sequence current | 20A/0.2V | |
Accuracy | Phase current | 0.5S/5P10 |
Zero-sequence current | 10P10,(1%-120%)In < 1% | |
Implementation method | Low power electromagnetic type | |
Load impedance | ≥ 20 kΩ | |
Temperature range | -40℃ -70℃ | |
Electronic-typeVoltage Sensor | ||
Rated voltage ratio | Phase current | 10kv, 3.25V |
Zero-sequence current | 6.5V | |
Accuracy | Phase current | 0.5 |
Zero-sequence current | 1 | |
Implementation method | Resistance division pressure | |
Temperature range | -40℃ -70℃ | |
Partial release | At 14.4kV, 10 pC | |
Load impedance | Terminal input impedance >10KΩ Distribution line loss collection module input impedance >10 MΩ Comprehensive impedance >5MΩ |
|
Electromagnetic-type Voltage Transformer (external type) | ||
Quantity | 2 | |
Rated voltage ratio | 10kv / 0.1kv / 0.22kv | |
Accuracy | 0.5 | |
Capacity | 10/0.1 winding, 30VA10/0.22 winding, meet product power consumption requirements Rated capacity ≥ 150VA Short-time capacity ≥ 300VA/1s |
If you didn’t know which switchgear system that used to your present project, it’s time to speak to our Industry Experts-Kimball. We’re glad to answer any questions you may have!
”From planning to delivery, it has been a smooth and gratifying transaction. The Dongshenyuan Electric team is quickly responsive, and the quality of DSY Switchgear are top-grade! In the end, they deliver as promised, and more. We look forward to a long-term partnership with them.”
Manufacturer Of Switchgear For Power Distribution and Electricity Generation System In China for 20 years
© 2023 Migor Template Kit – All rights reserved.
Download our catalog to see all products and data sheets, the catalog sheet will be automatically sent to your email address.
Send us a message if you have any questions or request a quote. Our experts will give you a reply within 24 hours and help you select the right valve you want.
All of switchgear are customized for sampling